Note:
This project will be discontinued after December 13, 2021. [more]
Product:
Siprotec_5_with_cpu_variant_cp100
(Siemens)Repositories |
Unknown: This might be proprietary software. |
#Vulnerabilities | 4 |
Date | Id | Summary | Products | Score | Patch | Annotated |
---|---|---|---|---|---|---|
2021-09-14 | CVE-2021-33719 | A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Specially crafted packets sent to port 4443/tcp could cause a Denial-of-Service condition or potential remote code execution. | Siprotec_5_with_cpu_variant_cp050, Siprotec_5_with_cpu_variant_cp100, Siprotec_5_with_cpu_variant_cp300 | 9.8 | ||
2021-09-14 | CVE-2021-33720 | A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Specially crafted packets sent to port 4443/tcp could cause a Denial-of-Service condition. | Siprotec_5_with_cpu_variant_cp050, Siprotec_5_with_cpu_variant_cp100, Siprotec_5_with_cpu_variant_cp300 | 7.5 | ||
2021-09-14 | CVE-2021-37206 | A vulnerability has been identified in SIPROTEC 5 relays with CPU variants CP050 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP100 (All versions < V8.80), SIPROTEC 5 relays with CPU variants CP300 (All versions < V8.80). Received webpackets are not properly processed. An unauthenticated remote attacker with access to any of the Ethernet interfaces could send specially crafted packets to force a restart of the target device. | Siprotec_5_with_cpu_variant_cp050, Siprotec_5_with_cpu_variant_cp100, Siprotec_5_with_cpu_variant_cp300 | 7.5 | ||
2019-03-21 | CVE-2018-16563 | A vulnerability has been identified in Firmware variant IEC 61850 for EN100 Ethernet module (All versions < V4.35), Firmware variant MODBUS TCP for EN100 Ethernet module (All versions), Firmware variant DNP3 TCP for EN100 Ethernet module (All versions), Firmware variant IEC104 for EN100 Ethernet module (All versions), Firmware variant Profinet IO for EN100 Ethernet module (All versions), SIPROTEC 5 relays with CPU variants CP300 and CP100 and the respective Ethernet communication modules... | En100_ethernet_module_firmware, En100_ethernet_module_with_firmware_variant_dnp3_tcp, En100_ethernet_module_with_firmware_variant_iec104, En100_ethernet_module_with_firmware_variant_iec_61850, En100_ethernet_module_with_firmware_variant_modbus_tcp, En100_ethernet_module_with_firmware_variant_profinet_io, Siprotec_5_with_cpu_variant_cp100, Siprotec_5_with_cpu_variant_cp200, Siprotec_5_with_cpu_variant_cp300 | 5.9 |