Note:
This project will be discontinued after December 13, 2021. [more]
Product:
Simatic_s7\-1200_firmware
(Siemens)Repositories |
Unknown: This might be proprietary software. |
#Vulnerabilities | 10 |
Date | Id | Summary | Products | Score | Patch | Annotated |
---|---|---|---|---|---|---|
2012-10-10 | CVE-2012-3040 | Cross-site scripting (XSS) vulnerability in the web server on Siemens SIMATIC S7-1200 PLCs 2.x through 3.0.1 allows remote attackers to inject arbitrary web script or HTML via a crafted URI. | Simatic_s7\-1200_cpu_1211c_firmware, Simatic_s7\-1200_cpu_1212c_firmware, Simatic_s7\-1200_cpu_1212fc_firmware, Simatic_s7\-1200_cpu_1214_fc_firmware, Simatic_s7\-1200_cpu_1214c_firmware, Simatic_s7\-1200_cpu_1215_fc_firmware, Simatic_s7\-1200_cpu_1215c_firmware, Simatic_s7\-1200_cpu_1217c_firmware, Simatic_s7\-1200_firmware | N/A | ||
2012-09-25 | CVE-2012-3037 | The Siemens SIMATIC S7-1200 2.x PLC does not properly protect the private key of the SIMATIC CONTROLLER Certification Authority certificate, which allows remote attackers to spoof the S7-1200 web server by using this key to create a forged certificate. | Simatic_s7\-1200_cpu_1211c_firmware, Simatic_s7\-1200_cpu_1212c_firmware, Simatic_s7\-1200_cpu_1212fc_firmware, Simatic_s7\-1200_cpu_1214_fc_firmware, Simatic_s7\-1200_cpu_1214c_firmware, Simatic_s7\-1200_cpu_1215_fc_firmware, Simatic_s7\-1200_cpu_1215c_firmware, Simatic_s7\-1200_cpu_1217c_firmware, Simatic_s7\-1200_firmware | N/A | ||
2013-04-22 | CVE-2013-2780 | Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port). | Simatic_s7\-1200_cpu_1211c_firmware, Simatic_s7\-1200_cpu_1212c_firmware, Simatic_s7\-1200_cpu_1212fc_firmware, Simatic_s7\-1200_cpu_1214_fc_firmware, Simatic_s7\-1200_cpu_1214c_firmware, Simatic_s7\-1200_cpu_1215_fc_firmware, Simatic_s7\-1200_cpu_1215c_firmware, Simatic_s7\-1200_cpu_1217c_firmware, Simatic_s7\-1200_firmware | N/A | ||
2013-04-22 | CVE-2013-0700 | Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). | Simatic_s7\-1200_cpu_1211c_firmware, Simatic_s7\-1200_cpu_1212c_firmware, Simatic_s7\-1200_cpu_1212fc_firmware, Simatic_s7\-1200_cpu_1214_fc_firmware, Simatic_s7\-1200_cpu_1214c_firmware, Simatic_s7\-1200_cpu_1215_fc_firmware, Simatic_s7\-1200_cpu_1215c_firmware, Simatic_s7\-1200_cpu_1217c_firmware, Simatic_s7\-1200_firmware | N/A | ||
2019-12-12 | CVE-2019-13945 | A vulnerability has been identified in SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family < V4.x (incl. SIPLUS variants) (All versions), SIMATIC S7-1200 CPU family V4.x (incl. SIPLUS variants) (All versions with Function State (FS) < 11), SIMATIC S7-200 SMART CPU CR20s (6ES7 288-1CR20-0AA1) (All versions <= V2.3.0 and Function State (FS) <= 3), SIMATIC S7-200 SMART CPU CR30s (6ES7 288-1CR30-0AA1) (All versions <= V2.3.0 and Function State (FS) <=... | S7\-200_smart_firmware, Simatic_s7\-1200_firmware | N/A | ||
2018-12-13 | CVE-2018-13815 | A vulnerability has been identified in SIMATIC S7-1200 (All versions), SIMATIC S7-1500 (All Versions < V2.6). An attacker could exhaust the available connection pool of an affected device by opening a sufficient number of connections to the device. Successful exploitation requires an attacker to be able to send packets to port 102/tcp of the affected device. No user interaction and no user privileges are required to exploit the vulnerability. The vulnerability, if exploited, could cause a... | Simatic_s7\-1200_firmware, Simatic_s7\-1500_firmware | 7.5 |