Product:

Guardlogix_5580_firmware

(Rockwellautomation)
Repositories

Unknown:

This might be proprietary software.

#Vulnerabilities 13
Date Id Summary Products Score Patch Annotated
2024-06-14 CVE-2024-5659 Rockwell Automation was made aware of a vulnerability that causes all affected controllers on the same network to result in a major nonrecoverable fault(MNRF/Assert). This vulnerability could be exploited by sending abnormal packets to the mDNS port. If exploited, the availability of the device would be compromised. 1756\-En4_firmware, Compact_guardlogix_5380_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5580_firmware, Guardlogix_5580_firmware 6.5
2024-10-08 CVE-2024-8626 Due to a memory leak, a denial-of-service vulnerability exists in the Rockwell Automation affected products. A malicious actor could exploit this vulnerability by performing multiple actions on certain web pages of the product causing the affected products to become fully unavailable and require a power cycle to recover. 1756\-En4tr_firmware, Compact_guardlogix_5380_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5580_firmware, Guardlogix_5580_firmware 7.5
2024-08-14 CVE-2024-40619 CVE-2024-40619 IMPACT A denial-of-service vulnerability exists in the affected products. The vulnerability occurs when a malformed CIP packet is sent over the network to the device and results in a major nonrecoverable fault causing a denial-of-service. Controllogix_5580_firmware, Guardlogix_5580_firmware 7.5
2022-04-01 CVE-2022-1159 Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user. Compact_guardlogix_5380_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5580_firmware, Guardlogix_5580_firmware 7.2
2022-04-11 CVE-2022-1161 An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other. Compact_guardlogix_5370_firmware, Compact_guardlogix_5380_firmware, Compactlogix_1768\-L43_firmware, Compactlogix_1768\-L45_firmware, Compactlogix_1769\-L31_firmware, Compactlogix_1769\-L32c_firmware, Compactlogix_1769\-L32e_firmware, Compactlogix_1769\-L35cr_firmware, Compactlogix_1769\-L35e_firmware, Compactlogix_5370_l1_firmware, Compactlogix_5370_l2_firmware, Compactlogix_5370_l3_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5550_firmware, Controllogix_5560_firmware, Controllogix_5570_firmware, Controllogix_5580_firmware, Drivelogix_5730_firmware, Flexlogix_1794\-L34_firmware, Guardlogix_5560_firmware, Guardlogix_5570_firmware, Guardlogix_5580_firmware, Softlogix_5800_firmware 9.8
2022-06-02 CVE-2022-1797 A malformed Class 3 common industrial protocol message with a cached connection can cause a denial-of-service condition in Rockwell Automation Logix Controllers, resulting in a major nonrecoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online. Compact_guardlogix_5370_firmware, Compact_guardlogix_5380_firmware, Compactlogix_5370_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5570_firmware, Controllogix_5580_firmware, Guardlogix_5570_firmware, Guardlogix_5580_firmware 8.6
2022-07-27 CVE-2020-6998 The connection establishment algorithm found in Rockwell Automation CompactLogix 5370 and ControlLogix 5570 versions 33 and prior does not sufficiently manage its control flow during execution, creating an infinite loop. This may allow an attacker to send specially crafted CIP packet requests to a controller, which may cause denial-of-service conditions in communications with other products. Armor_compact_guardlogix_5370_firmware, Compact_guardlogix_5370_firmware, Compactlogix_5370_l1_firmware, Compactlogix_5370_l2_firmware, Compactlogix_5370_l3_firmware, Controllogix_5570_firmware, Guardlogix_5560_firmware, Guardlogix_5570_firmware, Guardlogix_5580_firmware 8.6
2022-12-19 CVE-2022-3752 An unauthorized user could use a specially crafted sequence of Ethernet/IP messages, combined with heavy traffic loading to cause a denial-of-service condition in Rockwell Automation Logix controllers resulting in a major non-recoverable fault. If the target device becomes unavailable, a user would have to clear the fault and redownload the user project file to bring the device back online and continue normal operation. Compact_guardlogix_5380_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Compactlogix_5580_firmware, Guardlogix_5580_firmware 7.5
2024-10-14 CVE-2024-6207 CVE 2021-22681 https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.PN1550.html  and send a specially crafted CIP message to the device. If exploited, a threat actor could help prevent access to the legitimate user and end connections to connected devices including the workstation. To recover the controllers, a download is required which ends any process that the controller is running. Compact_guardlogix_5380_sil_2_firmware, Compact_guardlogix_5380_sil_3_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5580_firmware, Controllogix_5580_process_firmware, Factorytalk_logix_echo_firmware, Guardlogix_5580_firmware 7.5
2024-09-12 CVE-2024-6077 A denial-of-service vulnerability exists in the Rockwell Automation affected products when specially crafted packets are sent to the CIP Security Object. If exploited the device will become unavailable and require a factory reset to recover. 1756\-En4_firmware, Compact_guardlogix_5380_sil_2_firmware, Compact_guardlogix_5380_sil_3_firmware, Compactlogix_5380_firmware, Compactlogix_5480_firmware, Controllogix_5580_firmware, Guardlogix_5580_firmware 7.5