Product:

Infrasuite_device_master

(Deltaww)
Repositories

Unknown:

This might be proprietary software.

#Vulnerabilities 31
Date Id Summary Products Score Patch Annotated
2023-07-10 CVE-2023-30765 ?Delta Electronics InfraSuite Device Master versions prior to 1.0.7 contain improper access controls that could allow an attacker to alter privilege management configurations, resulting in privilege escalation. Infrasuite_device_master 9.8
2023-07-10 CVE-2023-34316 ?An attacker could bypass the latest Delta Electronics InfraSuite Device Master (versions prior to 1.0.7) patch, which could allow an attacker to retrieve file contents. Infrasuite_device_master 7.5
2022-10-31 CVE-2022-38142 Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize user-supplied data provided through the Device-Gateway service port without proper verification. An attacker could provide malicious serialized objects to execute arbitrary code upon deserialization. Infrasuite_device_master 9.8
2022-10-31 CVE-2022-41776 Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to trigger the WriteConfiguration method, which could allow an attacker to provide new values for user configuration files such as UserListInfo.xml. This could lead to the changing of administrative passwords. Infrasuite_device_master 7.5
2022-10-31 CVE-2022-41644 Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lacks authentication for a function that changes group privileges. An attacker could use this to create a denial-of-service state or escalate their own privileges. Infrasuite_device_master 8.8
2022-10-31 CVE-2022-41772 Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior mishandle .ZIP archives containing characters used in path traversal. This path traversal could result in remote code execution. Infrasuite_device_master 9.8
2022-10-31 CVE-2022-41779 Delta Electronics InfraSuite Device Master versions 00.00.01a and prior deserialize network packets without proper verification. If the device connects to an attacker-controlled server, the attacker could send maliciously crafted packets that would be deserialized and executed, leading to remote code execution. Infrasuite_device_master 9.8
2022-10-31 CVE-2022-40202 The database backup function in Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior lacks proper authentication. An attacker could provide malicious serialized objects which, when deserialized, could activate an opcode for a backup scheduling function without authentication. This function allows the user to designate all function arguments and the file to be executed. This could allow the attacker to start any new process and achieve remote code execution. Infrasuite_device_master 9.8
2022-10-31 CVE-2022-41629 Delta Electronics InfraSuite Device Master versions 00.00.01a and prior allow unauthenticated users to access the aprunning endpoint, which could allow an attacker to retrieve any file from the “RunningConfigs” directory. The attacker could then view and modify configuration files such as UserListInfo.xml, which would allow them to see existing administrative passwords. Infrasuite_device_master 9.1
2022-10-31 CVE-2022-41657 Delta Electronics InfraSuite Device Master Versions 00.00.01a and prior allow attacker provided data already serialized into memory to be used in file operation application programmable interfaces (APIs). This could create arbitrary files, which could be used in API operations and could ultimately result in remote code execution. Infrasuite_device_master 9.8